Use our template to perform batch calculations for up to 1, tags in a single click. Then review, verify or share information with project teams across your enterprise. Choose the tags to include in your project report with optional units of measure and languages. Whether you're an experienced Engineer or a new graduate, our software enables thermowell process design without deep calculation knowledge. Temperature is the most measured variable in process the industry.
Even small measurement errors can have a detrimental effect on efficiency, energy consumption, product quality or safety. Maximize plant operating performance from start-up to shutdown with Emerson service technicians.
CEU-certified standard and customized training for specifications, commissioning, and operations. Emerson is where technology and engineering come together to create solutions for the benefit of our customers, driven without compromise for a world in action.
Please contact us for assistance. When the Strouhal Frequency approaches the natural frequency of the thermowell, it can lock-in to the natural frequency causing resonance, with greatly magnified forces. To prevent lock-in, the natural frequency of the thermowell must be higher than either the in-line or the transverse resonance condition. Operation through the in-line resonance is acceptable only if the cyclic stresses at the resonance condition are acceptably small.
The fluid velocity at which resonance occurs is referred to as a velocity critical. There are two velocity criticals for each natural frequency of the thermowell: one describing the transverse and the other describing the in-line response.
Since in-line force fluctuates at twice the frequency of the transverse force, the corresponding velocity critical is approximately one half that requires for transverse resonance. If the natural frequency of the thermowell overlaps either fs or 2fs, a large resonant buildup in vibration amplitude can occur.
The major cause of thermowell failure is fatigue due to resonance. A high enough level of damping may allow the thermowell to operate at the in-line or even the transverse resonance frequencies. In addition to frequency limits, the stresses within the thermowell and forces applied are also critical to evaluating the suitability of a thermowell for a specific process application. The 4 quantitative criteria to be evaluated are:. Resonant frequency of the thermowell must be sufficiently high so that destructive oscillations are not excited by the fluid flow.
The steady-state s-s fluid velocity should meet one of the following conditions:. Steady-state stresses are the result of hydrostatic fluid pressure and non-oscillating drag forces on the thermowell, and are calculated at the location of maximum stress. If the thermowell is partially shielded or has a reduced tip, the calculation must be performed with those considerations.
The maximum steady- state stress on the thermowell at design velocity must not exceed the allowable stress as determined by the Von Mises Criteria. The online thermowell calculation can help with preliminary calculations and official documentation with the R21 report. Also, this thermowell calculations whitepaper describes the updated standard and calculations in more detail. The Rosemount Temperature team, who performs more than 35, calculations for process manufacturers each year, can provide you with a formal R21 report to document the design to be in accordance with the PTC MP3 iTunes.
We invite you to follow us on Facebook, LinkedIn, Twitter and YouTube to keep up to date on all the latest news, events and innovations to help you take on and solve your toughest challenges. Please do, Just link back to the post and send us a quick note so we can share your work.
The opinions expressed here are the personal opinions of the authors. Content published here is not read or approved by Emerson before it is posted and does not necessarily represent the views and opinions of Emerson. Share this Display Dial Thermometers Digital Indicators. Switch Float Switches Optoelectronic Switches. Electronics Accessories Engineered Solutions. Primary Flow Elements.
Flow Switches. Air Flow Sensors. Display Gas Density Indicators. Transmit Gas Density Sensors. WIKA Part of your business Solutions for pressure, temperature, force and level measurement, flow measurement, calibration and SF 6 gas solutions from WIKA are an integral component of our customers' business processes.
Home Knowledge Software Thermowells Knowledge.